Es werden lediglich Traps mit Status CRITICAL oder WARNING aufgeführt!
Die Traps sollten mit allen APC Geräten funktionieren.
EVENT communicationLost .1.3.6.1.4.1.318.0.1 "Status Events" CRITICAL FORMAT APC UPS: Communication failure: Communication lost between the agent and the UPS. EVENT upsOverload .1.3.6.1.4.1.318.0.2 "Status Events" CRITICAL FORMAT APC UPS: UPS overload: The UPS has sensed a load greater than 100% of its rated capacity. EVENT upsDiagnosticsFailed .1.3.6.1.4.1.318.0.3 "Status Events" CRITICAL FORMAT APC UPS: Failed self-test: The UPS has failed its internal self-test. EVENT upsDischarged .1.3.6.1.4.1.318.0.4 "Status Events" CRITICAL FORMAT APC UPS: batteries are discharged: The UPS batteries are discharged. EVENT lowBattery .1.3.6.1.4.1.318.0.7 "Status Events" CRITICAL FORMAT APC UPS: Low battery: The UPS system's batteries are low and will soon be exhausted. EVENT contactFault .1.3.6.1.4.1.318.0.18 "Status Events" CRITICAL FORMAT APC M-UPS: Contact fault: A Measure-UPS contact closure has faulted. EVENT hardwareFailureBypass .1.3.6.1.4.1.318.0.20 "Status Events" CRITICAL FORMAT APC UPS: On bypass due to hardware failure: The UPS is on bypass due to a hardware failure. EVENT baseFanFailure .1.3.6.1.4.1.318.0.25 "Status Events" CRITICAL FORMAT APC UPS: Base module fan needs repair: The base module fan needs repair. EVENT outletOn .1.3.6.1.4.1.318.0.41 "Status Events" WARNING FORMAT APC PDU: State change.: An OUTLET has been turned on EVENT outletOff .1.3.6.1.4.1.318.0.42 "Status Events" WARNING FORMAT APC PDU: State change.: An OUTLET has turned off. EVENT outletReboot .1.3.6.1.4.1.318.0.43 "Status Events" WARNING FORMAT APC PDU: State change.: An OUTLET has rebooted. EVENT configChangeSNMP .1.3.6.1.4.1.318.0.44 "Status Events" WARNING FORMAT APC: State change.: The SNMP configuration has been changed. EVENT configChangeOutlet .1.3.6.1.4.1.318.0.45 "Status Events" WARNING FORMAT APC PDU: State change.: An outlet configuration has been changed. EVENT accessViolationConsole .1.3.6.1.4.1.318.0.46 "Status Events" WARNING FORMAT APC: Access violation.: Three unsuccessful logins have been attempted. EVENT accessViolationHTTP .1.3.6.1.4.1.318.0.47 "Status Events" WARNING FORMAT APC: Access violation.: An unsuccessful attempt to login via HTTP. EVENT passwordChange .1.3.6.1.4.1.318.0.48 "Status Events" WARNING FORMAT APC: Password change.: Someone has changed the password on the PDU. EVENT badVoltage .1.3.6.1.4.1.318.0.49 "Status Events" WARNING FORMAT APC UPS: Bad output voltage.: The output voltage is not within acceptable range. EVENT chargerFailure .1.3.6.1.4.1.318.0.51 "Status Events" WARNING FORMAT APC UPS: The battery charger has failed.: The battery charger has failed. EVENT batteryOverTemperature .1.3.6.1.4.1.318.0.53 "Status Events" WARNING FORMAT APC UPS: The battery temperature threshold has been violated.: The battery temperature threshold has been violated. EVENT smartRelayFault .1.3.6.1.4.1.318.0.55 "Status Events" WARNING FORMAT APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault.: SmartBoost(TM) or SmartTrim(TM) relay fault. EVENT humidityViolation1 .1.3.6.1.4.1.318.0.57 "Status Events" WARNING FORMAT APC UPS: Probe 1 humidity threshold violated.: Probe 1 humidity threshold violated. EVENT temperatureViolation1 .1.3.6.1.4.1.318.0.59 "Status Events" CRITICAL FORMAT APC MEASURE-UPS: A temperature threshold has been violated on probe 1.: A temperature threshold has been violated on probe 1. EVENT humidityViolation2 .1.3.6.1.4.1.318.0.61 "Status Events" CRITICAL FORMAT APC MEASURE-UPS: A humidity threshold has been violated on probe 2.: A humidity threshold has been violated on probe 2. EVENT temperatureViolation2 .1.3.6.1.4.1.318.0.63 "Status Events" CRITICAL FORMAT APC MEASURE-UPS: A temperature threshold has been violated on probe 2.: A temperature threshold has been violated on probe 2. EVENT mupsCommunicationLost .1.3.6.1.4.1.318.0.66 "Status Events" CRITICAL FORMAT APC MUPS: MUPS Communication failure: Communication lost between the agent and the MUPS.